Duplex Time-Dose Pump Control Panel
Duplex time-dose control with automatic lead/lag alternation · TELE E1ZI10 timer + E1ZMLA10 alternator · 120/240 VAC field selectable. UL 508A Listed, file E547664. LE-6002 is the panel only; LE-6004 includes all three floats.
On this panel a high-water condition does not stop pumping — it escalates it: the Alarm/HWLA float drives the red beacon and horn AND the R1 relay runs BOTH pumps simultaneously until the level clears. Never override or disable the high-water alarm. Voltage is field selectable by grouping pin: pin installed = 120 V · the pin MUST be removed for 240 V. Verify with a voltage tester before energizing; a neutral is required in both configurations. Disconnect at the main disconnect and use lockout/tagout before opening the panel.
Documents
Quick Start Guide Operation Manual Specification SheetAt a glance
- Models
- LE-6002 (panel only) · LE-6004 (all three floats included) — part numbers CP-001-6-0002 / 6-0004
- Supply
- 120/240 VAC, 60 Hz, single phase — one feed powers both pump circuits, the control logic and the alarm · grouping-pin selectable · neutral required
- Pumps
- Two pump circuits · 1 HP @ 120 VAC or 2 HP @ 240 VAC per pump · up to 20 FLA per pump · 25 A two-pole breaker per pump · total FLA 40 A · SCCR 5 kA
- Feeder
- Field supplied, upstream at the feeder panel — 50 A breaker recommended · field-supplied main disconnect required
- Control
- Duplex alternating time dose — TELE E1ZI10 asymmetrical timer sets the dose and pause · TELE E1ZMLA10 alternator switches lead/lag after each cycle · three floats: Timer Enable (lowest) · Override (middle, continuous run during high inflow) · Alarm/HWLA (highest)
- High water
- Red beacon + 85–95 dB horn with silence switch and test push-button · the R1 relay runs BOTH pumps simultaneously while the alarm annunciates
- Controls
- Two 3-position pump selectors (AUTO / OFF / ON) · pump run indicators
- Enclosure
- NEMA 4X polycarbonate, lockable quick latch · 10.3 × 13.28 × 5.8 in (W × H × D) · mounting height 11.32 in · –10 to 60 °C
- Compliance
- UL 508A Listed · file E547664 · NFPA 70 (NEC)