Control panel documentation

Duplex Pump Control Panel

LE-6001 / LE-6003 · CP-001-6-0001 / 6-0003

Duplex float control with automatic lead/lag alternation · 120/240 VAC field selectable · optional High Level Lag Activation. UL 508A Listed, file E547664. LE-6001 is the panel only; LE-6003 includes the floats.

Read first — 120/240 V selection

Field selectable by grouping pin: pin installed = 120 V · the pin MUST be removed for 240 V operation. Verify the pin against the connection diagram and confirm panel voltage with a voltage tester before energizing — incorrect configuration can damage connected equipment. A neutral conductor is required in both configurations. Disconnect at the main disconnect and use lockout/tagout before opening the panel. Never override or disable the high-water alarm.

Documents

Quick Start Guide The field sequence in four pages — mounting, 120/240 grouping-pin check, pump and float landings (Off · On · HLLA · High Water), alternation test, TELE E1ZMLA10 factory settings · line drawing v1.4 and 120 V connection diagram included · PDF Operation Manual Installation, wiring, operation, TELE E1ZMLA10 alternator programming, maintenance, troubleshooting, warranty · line drawing and 120 V / 240 V connection diagrams included · PDF Specification Sheet Ratings, float system & operation, alternation and high-demand behavior, compliance notes · PDF

At a glance

Models
LE-6001 (panel only) · LE-6003 (floats included) — part numbers CP-001-6-0001 / 6-0003
Supply
120/240 VAC, 60 Hz, single phase — one feed powers both pump circuits, the control logic and the alarm · grouping-pin selectable · neutral required
Pumps
Two pump circuits · 1 HP @ 120 VAC or 2 HP @ 240 VAC per pump · up to 20 FLA per pump · 25 A two-pole breaker per pump · total FLA 40 A · SCCR 5 kA
Feeder
Field supplied, upstream at the feeder panel — 50 A breaker recommended · field-supplied main disconnect required
Control
Duplex alternating float control — TELE E1ZMLA10 load alternator switches lead/lag after every cycle for balanced wear · Off / On / High Water floats + optional HLLA float that runs BOTH pumps during high demand · 2-, 3- and 4-float configurations
Alarm
High water — red beacon + horn · alarm test / mute switch · alarm circuit 5 A max. High water drives the alarm only; pump operation is unaffected.
Controls
Two 3-position pump selectors (AUTO / OFF / ON) · pump run indicators
Enclosure
NEMA 4X polycarbonate · 10.3 × 13.28 × 5.8 in (W × H × D) — exterior / mounting dimensions
Compliance
UL 508A Listed · file E547664 · NFPA 70 (NEC)

Support & warranty

End users: contact the authorized dealer or installer who supplied your system for all technical support, service calls, alarm response and warranty claims. Their details are recorded on the Service & Support card in the operation manual.

Dealer & sales enquiries: Legacy Controls · (321) 284-8592 · support@legacy-controls.com

Two (2) year limited warranty to the original purchaser, administered through the authorized dealer.