Control panel documentation

Simplex Time Dose Pump Control Panel

LE-4002 / LE-4004 · CP-001-4-0002 / 4-0004

Cyclic time-dose simplex pump control · Elko CRM-2H_UNI asymmetrical timer · 120/240 VAC field selectable · 3-float control. UL 508A Listed, file E547664. LE-4002 is the panel only; LE-4004 includes the float switch set.

Read first — 120/240 V selection

Ships configured for 120 V with a grouping pin between Terminal 2 and Neutral — remove the pin for 240 V and verify with a multimeter before energizing. A neutral is required even at 240 V — the alarm and control devices operate at 120 V. De-energize the panel and verify with a voltage tester before opening it. There are no overload devices in this panel; high water is alarm only and never interrupts the pump.

Documents

Operation Manual Installation, wiring, operation, Elko CRM-2H timer programming, maintenance, troubleshooting, warranty · line drawing and connection diagram included · PDF Specification Sheet Ratings, float configuration & application, product dimensions, compliance notes · PDF Troubleshooting Guide Device-classified symptom matrix — power & feeds, grouping pin, floats, CRM-2H timer, overloads, alarm circuit · PDF

At a glance

Models
LE-4002 (panel only) · LE-4004 (with float set) — part numbers CP-001-4-0002 / 4-0004
Voltage
Dual 120/240 VAC single phase, field selectable by grouping pin — pin installed = 120 V (factory default), pin removed = 240 V
Pump
Single pump, up to 20 FLA — 1 HP @ 120 VAC or 2 HP @ 240 VAC
Control
3-float time-dose control with Elko CRM-2H_UNI asymmetrical timer — On float (timer enable, lowest) · Override float (middle, bypasses the timer during high inflow) · High Water float (highest, alarm only)
Alarm
Red beacon + 85–95 dB buzzer · alarm test button · buzzer ON/OFF switch · alarm circuit limited to 5 A
Protection
25 A MCB for pump + IEC contactor · 5 A MCB for the segregated control circuit. Overload protection is integral to the pump motor — there are no overload devices in this panel. High water is alarm only and never interrupts the pump.
Supply circuit
Minimum supply circuit ampacity 30 A (25 A pump branch + 5 A alarm & control circuit branch), single feed · field-supplied main disconnect and feeder breaker
Enclosure
Type 4X polycarbonate, indoor/outdoor · body 10 × 8.4 × 5.2 in · overall 10.3 × 13.28 × 5.8 in incl. mounting flanges · approx. 7 lbs
Compliance
UL 508A Listed · file E547664

Support & warranty

End users: contact the authorized dealer or installer who supplied your system for all technical support, service calls, alarm response and warranty claims. Their details are recorded on the Service & Support card in the operation manual.

Dealer & sales enquiries: Legacy Controls · (321) 284-8592 · support@legacy-controls.com

Two (2) year limited warranty to the original purchaser, administered through the authorized dealer.