Control panel documentation

Simplex Pump Control Panel

LE-4001 / LE-4003 · CP-001-4-0001 / 4-0003

Demand (float-controlled) simplex pump control · 120/240 VAC field selectable · 3-float or 2-float configuration. UL 508A Listed, file E547664. LE-4001 is the panel only; LE-4003 includes the float switch set.

Read first — control-circuit feed & 120/240 V selection

A factory wire jumper powers the control circuit from L1 — the panel will not operate without it. Where a separate 120 V control-circuit feed is installed instead (jumper removed), THAT FEED STAYS ENERGIZED when the main feed is off — disconnect every feed and verify with a voltage tester before opening the panel. Ships configured 120 V (grouping pin between Terminal 2 and Neutral); remove the pin for 240 V and verify with a multimeter before energizing. A neutral is required even at 240 V — the control circuit operates at 120 V.

Documents

Quick Start Guide The field sequence in four pages — mounting, 120/240 grouping-pin check, control-circuit jumper, pump and float landings, Configuration A/B floats, start-up and functional test · PDF Operation Manual Installation, wiring, float configurations A/B, operation, maintenance, troubleshooting, warranty · line drawing and connection diagram included · PDF Specification Sheet Ratings, float configuration & application, product dimensions, compliance notes · PDF Troubleshooting Guide Device-classified symptom matrix — power & feeds, grouping pins, floats, overloads, alarm circuit · PDF

At a glance

Models
LE-4001 (panel only) · LE-4003 (with float set) — part numbers CP-001-4-0001 / 4-0003
Voltage
Dual 120/240 VAC single phase, field selectable by grouping pin — pin installed = 120 V (factory default), pin removed = 240 V
Pump
Single pump, up to 20 FLA — 1 HP @ 120 VAC or 2 HP @ 240 VAC
Control
3-float demand control (On · Off · High Water) with R1 logic relay for full drawdown — field configurable to 2-float via grouping pins
Alarm
Red beacon + 85–95 dB buzzer · alarm test button · buzzer ON/OFF switch · alarm circuit limited to 5 A
Protection
25 A MCB for pump + IEC contactor · 5 A MCB for the segregated control circuit. Overload protection is integral to the pump motor — there are no overload devices in this panel. High water is alarm only and never interrupts the pump.
Supply circuit
Minimum supply circuit ampacity 30 A (25 A pump branch + 5 A alarm & control circuit branch) · field-supplied main disconnect and feeder breaker
Enclosure
Type 4X polycarbonate, indoor/outdoor · body 10 × 8.4 × 5.2 in · overall 10.3 × 13.28 × 5.8 in incl. mounting flanges · approx. 7 lbs
Compliance
UL 508A Listed · file E547664

Support & warranty

End users: contact the authorized dealer or installer who supplied your system for all technical support, service calls, alarm response and warranty claims. Their details are recorded on the Service & Support card in the operation manual.

Dealer & sales enquiries: Legacy Controls · (321) 284-8592 · support@legacy-controls.com

Two (2) year limited warranty to the original purchaser, administered through the authorized dealer.