Aerobic Treatment Control Panel
CP-001-3-0006-240V
Time-based dosing · UV disinfection · failsafe lockout. 240 VAC pump circuit, 120 VAC control. UL 508A Listed, file E547664.
Read first — two power feeds
TWO separate feeds. The 240 V main powers only the spray/dose pump; a dedicated 120 V control circuit powers the air compressor, UV, alarms and timer — and it stays energized when the 240 V main is OFF. Disconnect BOTH and verify with a voltage tester before opening the panel. Neutrals from both feeds must land on the same neutral bus.
Documents
Operation Manual Specification SheetAt a glance
- Model
- CP-001-3-0006-240V
- Main power
- 240 VAC, 60 Hz, single phase — powers the spray/dose pump only
- Control power
- 120 VAC dedicated feed — compressor, UV, alarm and timer
- Spray / dose pump
- 240 V, up to 2 HP (20 FLA)
- Compressor
- 120 V, ¼ HP (5.0 FLA) — panel rated ½ HP max
- Timer
- Elko SHT-13/2 Wi-Fi smart timer, with run-time hour meter
- Protection
- Air loss or UV fault locks out the spray/dose pump. The timer enable float blocks short doses. High water raises the alarm only — the pump stays on schedule by design.
- Enclosure
- Polycase ZH-100804 · NEMA 4X polycarbonate · 10.0 × 8.4 × 5.2 in
- Compliance
- UL 508A Listed · file E547664 · NSF/ANSI 40 compatible